Product Description
The equipment is specially designed for energy saving system,makes use of advanced technology,
supplies leaving water of above -20℃ and can steadily control temperature of mould below -5℃.
The product is controlled by computer system,automatically running,
easy to be operated and clearly shown on liquid crystal display in Chinese.
Specification
Specification and parameter of low temperature(module)air cooling chiller
Model | STDF | -10 | -12 | -15 | -20 | -25 | -30 | -40 | -50 | -60 | -80 | -100 | |
Cooling Capacity | Kw | 11.8 | 13.9 | 18.4 | 26.2 | 33.1 | 36.8 | 52.4 | 66.2 | 73.6 | 104.8 | 132.4 | |
Kcal/h | 10148 | 11954 | 15824 | 22532 | 28466 | 31648 | 45064 | 56932 | 63296 | 90128 | 113864 | ||
Refrigerant | R22/R404A | ||||||||||||
Voltage | 3/N/PE AC 380/220V 50HZ | ||||||||||||
Control mode | Siemens PLC all Chinese display programmable controller | ||||||||||||
Protection function | Refrigeration high and low pressure protection, water system fault protection, antifreeze protection, compressor overheating | ||||||||||||
Quantity of compressors | set | 1 | 1 | 1 | 1or2 | 1or2 | 2 | 2or4 | 2or4 | 4 | 4 | 4 | |
Power for compressor | Kw | 5.98 | 7.01 | 8.82 | 12.01 | 15.12 | 17.64 | 24.02 | 30.24 | 35.28 | 35.28 | 60.48 | |
Ambient temperature | ℃ | ≤35 | |||||||||||
Power for fan | Kw | 0.96 | 0.96 | 1.10 | 1.35 | 1.35 | 1.65 | 1.65 | 2.20 | 2.20 | 3.60 | 4.40 | |
Chilled
water |
Inlet/outlet water temperature | ℃ | -10~-5 | ||||||||||
Water flow | T/h | 8 | 10 | 12 | 15 | 20 | 20 | 25 | 25 | 30 | 40 | 50 | |
Water resistance | Mpa | ≤0.07 | |||||||||||
Tube diameter | Flange thread | DN40 | DN50 | DN50 | DN65 | DN65 | DN65 | DN65 | DN65 | DN80 | DN80 | DN80 | |
Dimension | L | Mm | 1500 | 1500 | 1600 | 2000 | 2300 | 2400 | 2600 | 2900 | 3200 | 4500 | 5500 |
W | Mm | 1100 | 1100 | 1200 | 1300 | 1300 | 1300 | 1500 | 1500 | 1600 | 1600 | 2000 | |
H | Mm | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | 1400 | 1500 | 1500 | 1800 | |
Weight | kg | 350 | 450 | 500 | 550 | 700 | 950 | 1200 | 1400 | 1800 | 2500 | 5000 |
Specification and parameter of low temperature(module)air cooling chiller
Model | STDF | -10 | -12 | -15 | -20 | -25 | -30 | -40 | -50 | -60 | -80 | -100 | ||||||
Cooling Capacity | Kw | 11.8 | 13.9 | 18.4 | 26.2 | 33.1 | 36.8 | 52.4 | 66.2 | 73.6 | 104.8 | 132.4 | ||||||
Kcal/h | 10148 | 11954 | 15824 | 22532 | 28466 | 31648 | 45064 | 56932 | 63296 | 90128 | 113864 | |||||||
Refrigerant | R22/R404A | |||||||||||||||||
Voltage | 3/N/PE AC 380/220V 50HZ | |||||||||||||||||
Control mode | Siemens PLC all Chinese display programmable controller | |||||||||||||||||
Protection function | Refrigeration high and low pressure protection, water system fault protection, antifreeze protection, compressor overheating | |||||||||||||||||
Quantity of compressors | set | 1 | 1 | 1 | 1or2 | 1or2 | 2 | 2or4 | 2or4 | 4 | 4 | 4 | ||||||
Power for compressor | Kw | 5.98 | 7.01 | 8.82 | 12.01 | 15.12 | 17.64 | 24.02 | 30.24 | 35.28 | 35.28 | 60.48 | ||||||
Cooling
water |
Inlet/outlet water temperature | ℃ | 30/35 | |||||||||||||||
Water flow | T/h | 8 | 10 | 12 | 15 | 20 | 20 | 25 | 30 | 40 | 50 | 60 | ||||||
Water resistance | Mpa | ≤0.17 | ||||||||||||||||
Tube diameter | Flange thread | DN50 | DN65 | DN80 | ||||||||||||||
Chilled
water |
Inlet/outlet water temperature | ℃ | -10~-5 | |||||||||||||||
Water flow | T/h | 8 | 10 | 12 | 15 | 20 | 20 | 25 | 25 | 30 | 40 | 50 | ||||||
Water resistance | Mpa | ≤0.07 | ||||||||||||||||
Tube diameter | Flange thread | DN50 | DN65 | DN80 | ||||||||||||||
Dimension | L | Mm | 1500 | 1500 | 1600 | 2000 | 2300 | 2400 | 2600 | 2900 | 3200 | 4500 | 5500 | |||||
W | Mm | 1100 | 1100 | 1200 | 1300 | 1300 | 1300 | 1500 | 1500 | 1600 | 1600 | 2000 | ||||||
H | Mm | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | 1400 | 1500 | 1500 | 1800 | ||||||
Weight | kg | 350 | 450 | 500 | 550 | 700 | 950 | 1200 | 1400 | 1800 | 2500 | 5000 |